Fa   |   Ar   |   En
   The experimental comparison of environmental impacts of some hfc's used instead of hcfc-22 [Hcfc-22 yerine kullanilan bazi hfc'lerin �evresel etkilerinin deneysel olarak karsilastirilmasi]  
   
نویسنده devecioǧlu a.g. ,oru� v.
منبع journal of thermal science and technology - 2016 - دوره : 36 - شماره : 1 - صفحه:99 -105
چکیده    In this study,the tewi values for r417a and r424a refrigerants instead of hcfc-22 gas which don't deplete ozone layer were calculated and then compared. for a split type air conditioning equipment,the energy consumption amounts were experimentally determined for the three different refrigerants at an average ambient temperature of 38c. the annual energy consumption that is the cooling requirement was evaluated for the specific operating hours in may-september period. as a result of calculations,direct impact of r424a with the higher gwp value was also higher. it was found that although energy consumptions for both r424a and r417a were less than that for r22 by 10%,their tewi values were to be higher with 2 to 4% because of their greater gwp magnitudes. � 2016 tibtd printed in turkey.
کلیدواژه Global warming; R417A; R424A; TEWI
آدرس dicle universitesi mohendislik fakoltesi makine mohendisligi bolomo diyarbakr, Turkey, dicle universitesi mohendislik fakoltesi makine mohendisligi bolomo diyarbakr, Turkey
 
     
   