   uhf detection of partial discharge in high-voltage air insulated switchgear using improved vivaldi antenna  
   
نویسنده nickpay mohammad-reza ,danaie mohammad ,amirabad farahani roohallah ,yari vahid ,goudarzikia karim
منبع journal of modeling and simulation in electrical and electronics engineering - 2025 - دوره : 5 - شماره : 2 - صفحه:11 -17
چکیده    Partial discharge (pd) is a major concern in high-voltage electrical equipment, and its detection is crucial for ensuring the reliability and safety of power systems. in high voltage (hv) air-insulated switchgear (ais), which is commonly used in the transmission and distribution of electrical power, pd can occur due to various factors such as insulation defects, voids, or impurities. detecting pd at an early stage is essential to prevent equipment failure and costly downtime. ultra-high frequency (uhf) detection methods are widely used for pd detection in hv ais, as they offer high sensitivity and the capability to detect pd signals over long distances. in this paper, we will discuss using vivaldi directional antennas for pd detection in hv ais, focusing on their advantages, challenges, and potential applications. the simulation was carried out using cst microwave studio, and the result revealed that the antenna has a wide impedance bandwidth of 100% in the range of 0.5 to 1.5 ghz with s11 ˂ -10. an average gain of 5 db and a maximum gain of 8.62 db are achieved at the operational frequency band.
کلیدواژه partial discharge (pd) ,uhf ,vivaldi antenna ,air insulated switchgear (ais)
آدرس tehran regional electric company, iran, semnan university, faculty of electrical and computer engineering, iran, tehran regional electric company, iran, tehran regional electric company, iran, tehran regional electric company, iran
پست الکترونیکی k-goudarzi@trec.co.ir
 
     
   
Authors
  
 
 

Copyright 2023
Islamic World Science Citation Center
All Rights Reserved