   maximum smoke temperature in non-smoke model evacuation region for semi-transverse tunnel fire  
   
نویسنده lou b. ,qiu y. ,long x.
منبع journal of applied fluid mechanics - 2017 - دوره : 10 - شماره : 4 - صفحه:1139 -1151
چکیده    Smoke temperature distribution in non-smoke evacuation under different mechanical smoke exhaust rates of semi-transverse tunnel fire were studied by fds numerical simulation in this paper. the effect of fire heat release rate (10mw 20mw and 30mw) and exhaust rate (from 0 to 160m³/s) on the maximum smoke temperature in non-smoke evacuation region was discussed. results show that the maximum smoke temperature in non-smoke evacuation region decreased with smoke exhaust rate. plug-holing was observed below the smoke vent when smoke exhaust rate increased to a certain value. smoke spreading distance can be divided into three stages according to changes of smoke exhaust rate. the maximum smoke temperature model concluded that the peak temperature rise at tunnel vault is proportional to 0.75 power of dimensionless fire power. the maximum temperature in non-smoke evacuation region decays exponentially with the increase of smoke exhaust rate. however smoke vent interval influences the dimensionless maximum temperature in nonsmoke evacuation region slightly. smoke vent interval influences the dimensionless maximum temperature in non-smoke evacuation region slightly.
کلیدواژه tunnel fire ,semi-transverse ventilation ,plugholing ,temperature distribution
آدرس south china university of technology, school of electric power, china, south china university of technology, school of electric power, china, south china university of technology, school of chemistry and chemical engineering, china
پست الکترونیکی 18502083731@163.com
 
     
   
Authors
  
 
 

Copyright 2023
Islamic World Science Citation Center
All Rights Reserved