Fa   |   Ar   |   En
   voltage unbalancing reduction in a stand-alone ac-dc hybrid microgrid based on floating compensation reference  
   
نویسنده tabatabaei hossein ,eliasi hussein ,najafi hamidreza
منبع international journal of industrial electronics, control and optimization - 2020 - دوره : 3 - شماره : 3 - صفحه:235 -247
چکیده    A hybrid ac-dc microgrid consists of an ac and a dc subgrid that are connected to each other through an interlinking converter (ic). the main function of an ic under islanded conditions is to transfer power between the two subgrids. in this paper, a scheme is presented to reduce the voltage unbalance factor in a hybrid acdc microgrid by using the free capacity of the ic. the free capacity of this converter is determined based on the current passing through each leg, and the amount of voltage unbalance compensation on the ac side of the microgrid is then obtained. the reference current of voltage unbalance compensation is calculated by using the positive, negative, and zero sequence components of the voltage of ic terminals. the total reference current is obtained by adding the reference current of voltage unbalance compensation and the current calculated for power transfer. furthermore, a proportionalresonant (pr) controller is used in the control system of the fourleg inverter. therefore, the reference current is properly tracked by the power stage of the inverter. simulation results verify the accuracy of the proposed scheme under different conditions.
کلیدواژه hybrid ac-dc microgrid ,interlinking converter ,power quality ,voltage unbalance
آدرس university of birjand, faculty of electrical and computer engineering, iran, university of birjand, faculty of electrical and computer engineering, iran, university of birjand, faculty of electrical and computer engineering, iran
پست الکترونیکی h.r.najafi@birjand.ac.ir
 
     
   
Authors
  
 
 

Copyright 2023
Islamic World Science Citation Center
All Rights Reserved