Faulty line selection method for distribution network based on variable scale bistable system
|
|
|
|
|
نویسنده
|
wang x. ,gao j. ,song g. ,cheng q. ,wei x. ,wei y.
|
منبع
|
journal of sensors - 2016 - دوره : 2016 - شماره : 0
|
چکیده
|
Since weak fault signals often lead to the misjudgment and other problems for faulty line selection in small current to ground system,this paper proposes a novel faulty line selection method based on variable scale bistable system (vsbs). firstly,vsbs is adopted to analyze the transient zero-sequence current (tzsc) with different frequency variety scale ratio and noise intensity,and the results show that vsbs can effectively extract the variation trends of initial stage of tzsc. secondly,tzsc is input to vsbs for calculation with runge-kutta equations,and the output signal is chosen as the characteristic currents. lastly,correlation coefficients of every line characteristic current are used as the index to a novel faulty line selection criterion. a large number of simulation experiments prove that the proposed method can accurately select the faulty line and extract weak fault signals in the environment with strong noise. © 2016 xiaowei wang et al.
|
|
|
آدرس
|
school of electrical engineering,xi'an jiaotong university,xi'an,shaanxi province, China, college of automation engineering,shanghai university of electric power,shanghai, China, school of electrical engineering,xi'an jiaotong university,xi'an,shaanxi province, China, college of automation engineering,shanghai university of electric power,shanghai, China, college of information and electrical engineering,china agricultural university,beijing, China, school of electrical engineering and automation,henan polytechnic university,jiaozuo, China
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Authors
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|