Fa   |   Ar   |   En
   Underside Corrosion of above Ground Storage Tanks (ASTs)  
   
نویسنده RIM-RUKEH A. ,OKOKOYO P. A.
منبع journal of applied sciences and environmental management - 2005 - دوره : 9 - شماره : 1 - صفحه:161 -163
چکیده    Underside corrosion of a failed above ground storage tank (ast) was investigated by the physiochemical analysis of water sample that was ingress between the tank bottom plate and the concrete foundation. the results of the water sample analysis showed ph (5.8), temperature (30°c), conductivity (4800 μs/cm), dissolved oxygen (3.5 mg/l), chloride (674 mg/l), carbonate (16.90mg/l) and nitrate (23.10 mg/l). the levels of the parameters studied were generally high and above statutory safe limits. the results showed that the physico-chemical characteristics of the water sample have diagnostic and predictive values to implicate and promote underside corrosion of the studied above ground storage tank.
آدرس College of Education, Integrated Science Department, Nigeria, College of Education, Chemistry Department, Nigeria
 
     
   
Authors
  
 
 

Copyright 2023
Islamic World Science Citation Center