   Energy and exergy analysis of a ceiling-type air conditioning system operating with different refrigerants  
   
نویسنده ozbek a.
منبع journal of engineering research - 2016 - دوره : 4 - شماره : 3 - صفحه:144 -162
چکیده    In this study,an energy and exergy analysis is applied to a ceiling-type air conditioning (ctac) system operating with various refrigerants. firstly,the hourly cooling load capacities of a sample building are determined for the months of april,may,june,july,august and september. the cooling load capacity is determined using the hourly analysis program (hap). secondly,the coefficient of performance (cop),exergy efficiency and exergy destruction values of the whole system,and each of its components,are determined. results indicate that the exergy destruction in the compressor,condenser and capillary tube decreases,when refrigerant r600a is used in the ctac system instead of refrigerant r404a,but the value of exergy destruction in the evaporator does not substantially change. when the refrigerant is changed from r404a to r600a,it is calculated that the power consumption and exergy destruction ratio of the air conditioning system decrease by 13.0% and 20.2%,respectively,but the exergy efficiency value is increased by 13.9%.
کلیدواژه Ceiling-type air conditioning system; Exergy analysis; Exergy destruction; Exergy efficiency; Exergy rate
آدرس department of mechanical engineering,ceyhan engineering faculty,cukurova university,adana, Turkey
 
     
   