Fa   |   Ar   |   En
   analysis of gasketed-plate heat exchanger performance using nanofluid  
   
نویسنده bozorgan navid ,shafahi maryam
منبع journal of heat and mass transfer research - 2017 - دوره : 4 - شماره : 1 - صفحه:65 -72
چکیده    A numerical analysis of the heat transfer and pressure drop of a water-based γ-al2o3 nanofluid gasketed plate heat exchanger was undertaken to specify its optimum conditions. the results showed that, based on the heat exchanger’s performance index, the optimal volume concentration of γ-al2o3 is approximately 0.016. the heat transfer rate at the optimal concentration of nanofluid is approximately 12.3% higher than that of pure water (base fluid), while the pumping power increased by 1.15%. increasing ϕ values from ϕ=0.016 to ϕ=0.028 will result in a 1% improvement in the heat transfer rate.
کلیدواژه nanofluid ,particle volume fraction ,gasketed-plate heat exchanger ,heat transfer ,pressure drop
آدرس islamic azad university, abadan branch, department of mechanical engineering, ایران, california state polytechnic university, mechanical engineering department, usa
پست الکترونیکی maryam.shafahi@email.ucr.edu
 
     
   
Authors
  
 
 

Copyright 2023
Islamic World Science Citation Center
All Rights Reserved