Fa   |   Ar   |   En
   optimizing naturally driven air flow in a vertical pipe by changing the intensity and location of the wall heat flux  
   
نویسنده rahimi m. ,khalafi-salout m.
منبع journal of computational and applied research in mechanical engineering - 2016 - دوره : 5 - شماره : 2 - صفحه:137 -145
چکیده    Heat transfer from the internal surfaces of a vertical pipe to the adjacent air gives rise to the air flow establishment within the pipe. with the aim of optimizing the convective air flow rate in a vertical pipe, the details of the flow and thermal fields were investigated in the present study. conservation equations of mass, momentum, and energy were solved numerically using simple implicit forwardmarching finite difference scheme for a twodimensional axissymmetric flow. in order to evaluate and optimize the air flow rate passing through the pipe, the position and intensity of the wall heat flux were altered when the total employed heat transfer rate was constant. based on the results of the numerical analysis, relatively more air flow rate was achieved when more intensified heat flux was employed at the lowest part of the vertical pipe. this finding was then validated using a simple experimental setup. the results of the present study could be useful in the design and application of buoyancyassisted natural ventilation systems.
کلیدواژه natural ventilation ,vertical pipe ,wall heat flux
آدرس university of mohaghegh ardabili, faculty of engineering, ایران, university of mohaghegh ardabili, faculty of engineering, ایران
 
     
   
Authors
  
 
 

Copyright 2023
Islamic World Science Citation Center
All Rights Reserved