Analysis of Flashover Voltages of Disc Type Insulator under Artificial Pollution Condition
|
|
|
|
|
نویسنده
|
ahmad f. ,khan q. ,alam a.
|
منبع
|
international journal of engineering - 2016 - دوره : 29 - شماره : 6 - صفحه:762 -768
|
چکیده
|
Tripping of overhead transmission lines in winter season/fog due to insulation failure has been foremost issue. huge quantity of overhead insulator in distribution and transmission network make pollution based flashover a vital risk to the uninterrupted and steady power supply. surface resistivity due to deposition of various environmental contaminants on insulator surface gets low, which initiates flow of high leakage current and leads to flashover around the insulator surface. in this paper, flashover voltage (fov) analysis of artificially polluted disc insulator carried out. numerous kind of soluble and non-soluble and their mixture contaminants exist in industrial, marine and desert regions are modeled and analyse insulator characteristics i.e. equivalent salt deposit density (esdd), non-soluble deposit density (nsdd), ph, surface conductivity and esdd/nsdd. by using fov and esdd characteristic an empirical model is proposed to determine the flashover voltage. comparative study of experimental and calculated values of fov also carried out.
|
کلیدواژه
|
Surface Conductivity ,Contaminants ,Equivalent Salt Deposit Density ,Flashover Voltage ,Non-soluble Deposit Density ,pH
|
آدرس
|
aligarh muslim university, department of electrical engineering, India, aligarh muslim university, department of electrical engineering, India, aligarh muslim university, department of electrical engineering, India
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Authors
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|