Fa   |   Ar   |   En
   Determination of Electric Field at Inception Based upon Current-Voltage Characteristics of AC Corona in Rod-Plane Gaps  
   
نویسنده Javadi H. ,Farzaneh M. ,Peyda A.
منبع iranian journal of electrical and electronic engineering - 2010 - دوره : 6 - شماره : 2 - صفحه:119 -128
چکیده    This paper deals with the measurement of ac corona inception voltage, vincp, atthe tip of a rod electrode using a hemispherically-capped rod-plane electrode configurationfor various rod radii with a short air gap. effects of atmospheric pressure and temperaturevariation on vincp are investigated experimentally. an empirical equation for the field form factors of the hemispherically capped rod-plane electrodes is proposed with its range ofapplicability. the obtained results are analyzed to derive a more accurate analytical equation for the calculation of the electric field at corona inception voltage, eincp, and theaverage of electric field distribution, emean.
کلیدواژه Electric field ,Corona Inception Voltage ,Rod-plane Electrodes ,Form Factor ,Atmospheric Correction Factor ,3-D Electric Field Simulation
آدرس power and water university of technology, Department of ElectricalEngineering, ایران, Université du Québec à Chicoutimi,Chicoutimi, NSERC/Hydro-Quebec/UQAC Industrial Chair on Atmospheric Icing of Power Network Equipment (CIGELE)and Canada Research Chair on Engineering of Power NetworkAtmospheric Icing (INGIVRE), Canada, Université du Québec à Chicoutimi, NSERC/Hydro-Quebec/UQAC IndustrialChair on Atmospheric Icing of Power Network Equipment (CIGELE)and Canada Research Chair on Engineering of Power NetworkAtmospheric Icing (INGIVRE), Canada
 
     
   
Authors
  
 
 

Copyright 2023
Islamic World Science Citation Center
All Rights Reserved