surge arrester monitoring under different operating conditions using bees-anfis
|
|
|
|
|
نویسنده
|
khodsuz m. ,seyyedbarzegar s.m
|
منبع
|
iranian journal of electrical and electronic engineering - 2019 - دوره : 15 - شماره : 1 - صفحه:151 -160
|
چکیده
|
The essential role of surge arresters is equipment protection against overvoltages to increase system reliability. different monitoring techniques have been used to diagnose surge arrester condition. leakage current analysis methods by the extraction resistive and capacitive components of leakage current are a conventional method for surge arrester monitoring. insufficient appropriate thresholds are most important restriction of these kinds of methods. in this paper, the impact of pollution, ultraviolet aging and varistors fault on harmonic spectrum of leakage current have been evaluated experimentally. real tests and examinations have been done on different metal oxide surge arresters to investigate effects of mentioned factors on leakage current harmonics. to show results performance, bees-adaptive network based fuzzy inference system has been applie
|
کلیدواژه
|
surge arrester ,harmonics analysis ,leakage current ,diagnostic ,bees-anfis
|
آدرس
|
university of science and technology of mazandaran, faculty of electrical and computer engineering, ایران, shahrood university of technology, faculty of electrical and robotic engineering, ایران
|
پست الکترونیکی
|
seyyedbarzegar@shahroodut.ac.ir
|
|
|
|
|
|
|
|
|
|
|
|